11.4.2 Connecting Requirement
The equipment's power supply 1 complies with IEC/EN 61000-3-2.
The equipment's power supply 1 complies with IEC/EN 61000-3-3 and can be connected to current supply
network.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-3 and can be connected to current supply
network.

11.4.3 Wired Remote Control Installation

Do not modify the length of the remote control cable. Otherwise, it will cause fire or electrical shock.
Be sure to turn off the main power before installing and connecting the remote control. Otherwise, it will cause the electrical shock.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, fire or electrical shock.
If passing the remote control cable through a wall, be sure to install a water trap above the cable. Otherwise, it will cause the
electrical shock.
Install in a flat surface to avoid warping of remote control, else damage to the LCD case or operation problems may result.
Avoid installing the remote control cable near refrigerant pipes or water pipes, else will cause electrical shock or fire.
Install the remote control cable at least 5 cm away from electric wires of other appliances to avoid miss operation (electromagnetic
noise).
Be sure to use only the accessory screws to avoid damage of remote control PCB.

Attached Accessories

No.
Name
(1)
Remote control
(2)
Remote control cable
Screw
(3)
(M4 machine pitched - 30 mm)
Screw
(4)
(M4 self-tapping - 14 mm)
WARNING
CAUTION
Qty.
Diagram
1
1
3
3
37
Remark
Length (15 m)
Installing the remote control to an outlet box
(embedded cable)
Installing the remote control to the wall
(exposed cable)