15.6
Indoor Fan Motor Operation
•
Type of indoor fan motor are shown in below table:
•
During Cool / Fan Mode,
DC fan motor Manual fan speed is based on remote control setting.
o
Remote
Control
-
Setting
Indoor fan tap
SHi
DC fan motor Auto fan speed is specified to repetition of 8 patterns (1 pattern: 10 seconds) and follows odor
o
cut control.
AC fan motor Manual fan speed is based on remote control setting.
o
AC fan motor Auto fan speed is determined in table below and follows odor cut control.
o
•
During Soft Dry Mode
DC fan motor Manual and Auto indoor fan speed is fixed at SLo regardless of remote control fan setting.
o
AC fan motor Manual and Auto indoor fan speed is fixed at Lo regardless of remote control fan setting.
o
Wall Mounted Type
(KA1E5 Series)
60 x 60 Cassette Type
(MA1E5 Series)
95 x 95 Cassette Type
(NA1E5 Series)
Slim Hide-away Type
(NA1E5 Series)
Low Pressure Hide-away Type
(MA1E5 Series)
High
-
Hi
Me+
Mode
Cool
Fan
Mode
Hi
Cool
●
Fan
Medium
-
Me
Me-
Hi
Me
●
●
●
●
Me
●
●
91
DC Fan Motor
AC Fan Motor
Low
-
Lo
Lo-
Lo
●
●
Lo
Stop
●
-
-
SLo
SSLo