Output Override - Danfoss ECL Comfort 210 Installation Manual

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide

6.6 Output override

The output override is used to disable one or more of the controlled
components. This could among others be useful in a service
situation.
Action:
Purpose:
Choose 'MENU' in any of the overview
displays
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Choose common controller settings
Confirm
Choose 'Output override'
Confirm
Choose a controlled component
Confirm
Adjust the status of the controlled
component:
Motorized control valve: AUTO, STOP,
CLOSE, OPEN
Pump: AUTO, OFF, ON
Confirm status change
Remember to change the status back again as soon as an override
is not required any longer.
Danfoss District Energy
ECL Comfort 210 / 310, application A231 / A331
Examples:
M1, P1 etc.
Controlled components
When the selected controlled component (output) is not 'AUTO' , the
ECL Comfort controller does not control the component in question
(pump or motorized control valve e.g.). Frost protection is not active.
VI.LG.P1.02
Circuit selector
DEN-SMT/DK
91