Installation Guide
Max. limitation of the desired flow temperature:
In the applications A231.1 and A331.1 the max. limitation value is
selectable in 'Temp. max. ' .
Temp. max. (flow temp. limit, max.) — A231.1 / A331.1
Circuit
1
Set the max. flow temperature for the system. The desired flow
temperature will not be higher than this setting. Adjust the factory
setting, if required.
Temp. min. (flow temp. limit, min.)
Circuit
1
Set the min. flow temperature for the system. The desired flow
temperature will not be lower than this setting. Adjust the factory
setting, if required.
56
DEN-SMT/DK
ECL Comfort 210 / 310, application A231 / A331
11178
Setting range
Factory setting
10 ... 150 °C
90 °C
11177
Setting range
Factory setting
10 ... 150 °C
10 °C
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.LG.P1.02
Danfoss District Energy