Danfoss ECL Comfort 210 Installation Manual page 64

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Low limit Y1 (flow / power limitation, low limit, Y-axis)
Circuit
1
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.
The corresponding X coordinate is set in 'High T out X1'.
Low T out X2 (flow / power limitation, low limit, X-axis)
Circuit
1
Set the outdoor temperature for the high flow / power limitation.
The corresponding Y coordinate is set in 'High limit Y2'.
High limit Y2 (flow / power limitation, high limit, Y-axis)
Circuit
1
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2'.
The corresponding X coordinate is set in 'Low T out X2'.
Adapt. time (adaptation time)
Circuit
1
Controls how fast the flow / power limitation adapts to the desired
limitation.
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted slowly.
50:
The desired temperature is adapted quickly.
Filter constant
Circuit
1
The actual filter dampens the flow / power input data by the set factor.
1:
No filtering.
2:
Fast (low filter constant)
50:
Slow (high filter constant)
64
DEN-SMT/DK
ECL Comfort 210 / 310, application A231 / A331
11117
Setting range
Factory setting
0.0 ... 999.9 l/h
999.9 l/h
11118
Setting range
Factory setting
-60 ... 20 °C
-15 °C
11116
Setting range
Factory setting
0.0 ... 999.9 l/h
999.9 l/h
11112
Setting range
Factory setting
OFF / 1 ... 50 s
OFF
11113
Setting range
Factory setting
1 ... 50
The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
10
VI.LG.P1.02
Danfoss District Energy