WarmFlow 50/70 Installation & Servicing page 26

Table of Contents

Advertisement

Terminal Position
A
Below gutters, soil pipes or drain pipes
B
From a door, window or air vent
C
Above ground, flat roof or balcony level
D
Below eaves or balconies
E
From an internal or external corner
F
From a terminal facing the terminal
G
From a surface facing the terminal
H
Vertically from a terminal on the same wall
I
Horizontally from the terminal on the same wall
J
Directly below an opening, air brick, window, etc.
K
From a vertical drain pipe or soil pipe
L
From a vertical structure on the side of the terminal
These are minimum dimensions and are only quoted as a guideline but they will
satisfy the requirements of all UK Building regulations.
Where the flue terminal is within 1 metre of any plastic material, such material
should be shielded from the effects of the combustion products of the flue.
Page 24
Min Distance
1,000
600
600
1,000
600
600
600
1,500
600
600
1,000
750