Specifications; Output Characteristics - National Instruments FIELDPOINT cFP-PWM-520 Operating Instructions Manual

Eight-channel, 5 v or 10–30 v pwm output module
Table of Contents

Advertisement

Specifications

The following specifications are typical for a range of –40 to 70 °C
unless otherwise noted.

Output Characteristics

Number of channels.......................... 8
Output type ....................................... Sourcing
Output voltage .................................. Supply voltage – (Output
Supply voltage .................................. 5 VDC or 10 to 30 VDC,
Maximum output current per channel
Module
cFP-PWM-520
FP-PWM-520
ON resistance
Revision E and later modules
Revision D and earlier
modules ...................................... 0.3 Ω
Pulse-width accuracy ........................ –1, +3 μs, any period and
Short-Circuit Protection
Minimum trip current
Revision E and later modules..... 9 A
Revision D and earlier
modules ...................................... 1 A
1
The letter in the part number identifies the revision of the module. For example, part
number 185715A-02 identifies a revision A cFP-PWM-520. The part number is
printed on a label on the module. On the FP-PWM-520, the label is on the bottom of
the module. On the cFP-PWM-520, the label is on the back of the module.
FP-PWM-520 and cFP-PWM-520
Temperature Ranges
–40 to 50 °C
1 A
1 A
12
current × Output impedance)
user-provided
50 to 60 °C
0.75 A
1 A
... 0.15 Ω
1
duty cycle
60 to 70 °C
0.5 A
1 A
ni.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fieldpoint fp-pwm-520

Table of Contents