3. LP (Liquid Propane) Gas Pipe Sizing

The following is intended for use for piping between a Single or Second Stage (Low Pressure) Regulator and the appliance. The
following tables list maximum capacity of pipe in cubic feet of gas per hour for an inlet pressure of 11 inches water column and specific
pressure drop of 0.5 inches water column based on 1.5 specific gravity for liquid propane.
Maximum Liquid Propane Delivery Capacity – Length of Corrugated Stainless Steel Pipe in Feet
Pipe Size
10
½"
129
¾"
303
1"
605
1 ¼"
971
1 ½"
1990
2"
4640
Table 15 – Liquid Propane Delivery Capacity – Corrugated Stainless Steel Pipe – Refer to ANSI Z223.1 – National Fuel Gas
Code, Latest Edition
Maximum Liquid Propane Delivery Capacity – Length of Black Iron Pipe (Sch. 40 Metallic) in Feet
Pipe Size
10
½"
291
¾"
608
1"
1150
1 ¼"
2350
1 ½"
3520
2"
6790
Table 16 – Liquid Propane Delivery Capacity – Black Iron Pipe – Refer to ANSI Z223.1 – National Fuel Gas Code, Latest Edition
B. GAS CONNECTION REQUIREMENTS
1. a. On 140F models: The gas connection fitting on the appliance is ½" male NPT. A ½" X ¾" Bell Coupling has been provided with the
appliance to aid installation. NOTE: The pipe size must not be less than ½".
b. On 199F models: The gas connection fitting on the appliance is ¾" male NPT. NOTE: The pipe size must not be less than ¾".
2. The supply line must be sized for the maximum output of the appliance being installed. If there are additional gas appliances from the
main supply line, measure the size of the supply line according to the COMBINED total maximum BTUH draw for the appliances as if
they were operating at the same time.
3. Measure the length of the gas supply line from the gas meter to the appliance. Appliance must be installed downstream of the gas
meter to ensure adequate gas supply. Use the tables in this manual or refer to the gas line manufacturer's sizing information to
determine the correct supply pipe size.
4. A manual gas shut-off valve should be installed in the gas supply line close to the appliance. See Figure 17 for detail.
5. To facilitate any future maintenance, it is also recommended that an approved gas union fitting be installed in the supply line between
the shut-off valve and the connection on the appliance.
6. Test the gas pressure to make sure it meets the minimum standards and does not exceed the maximum standards of the appliance.
7. Leak test the gas line pipe before placing the appliance in operation. Only use approved leak detector liquid solutions to check for
leaks.
8. Do not operate the appliance until all connections have been completed and the heat exchanger is filled with water.
Cubic Feet per Hour (0.60 Specific Gravity, 0.5 WC Pressure Drop)
20
30
91
74
216
177
153
425
344
297
661
528
449
1400
1140
988
3290
2680
2330
Cubic Feet per Hour (0.60 Specific Gravity, 0.5 WC Pressure Drop)
20
30
40
200
160
137
418
336
287
787
632
541
1620
1300
1110
2420
1940
1660
4660
3750
3210
40
50
60
64
58
53
137
126
265
241
397
359
884
805
2080
1900
50
60
122
110
255
231
480
434
985
892
1480
1340
2840
2570
80
100
150
45
41
31
109
98
75
208
186
143
307
270
217
696
621
506
1650
1480
1210
80
100
150
101
94
84
212
197
175
400
372
330
821
763
677
1230
1140
1010
2370
2200
1950
WHL-015 REV. 5.20.16
29
200
28
69
129
183
438
1050
200
67
140
265
543
814
1570