Exhaust Vent And Intake Pipe Sizing; Longer Vent Runs; Exhaust Vent And Intake Pipe Installation - Westinghouse WBMC**500 Manual

Installation start-up maintenance parts warranty commercial gas-fired boilers
Table of Contents

Advertisement

E. Exhaust Vent and Intake Pipe Sizing
1. The exhaust vent and intake pipe size is 4" for the 500 and
6" for the 850.
2. The maximum total equivalent length of exhaust vent and
intake pipe should not exceed 200 feet.
a. The equivalent length of elbows, tees, and other fittings
are listed in the Friction Loss Table.
Friction Loss Equivalent in Piping and Fittings
Fittings or Piping
90 Degree Elbow*
45 Degree Elbow
Coupling
Air Inlet Tee
Straight Pipe
V Series Vent Kit
AL20 4c Vent Terminal
Table 9 - *Friction loss for long radius elbow is 1 foot less. NOTE:
Consult Polypropylene venting instructions for friction loss and
pressure drop equivalents.
b. For example: If the exhaust vent is 4" in diameter, has
o
two 90
elbows, and 10 feet of PVC pipe we will calculate:
Exhaust Vent Equivalent Length = (2x3) + 10 = 20 feet.
Further, if the 4" intake pipe has two 90
elbow, and 10 feet of PVC pipe, the following calculation
applies:
Intake Pipe Equivalent Length = (2x3) + 1 + 10 = 23 feet.
The total equivalent length is 33 feet, well below the
maximum of 200 feet.
c. Effort should be made to keep a minimum difference in
equivalent length between the exhaust vent and intake
pipe.
3. The minimum total equivalent length is 16 feet.
Do not exceed the maximum lengths for vent pipes. Excessive
length could result in boiler shutdown and property damage.
Failure to provide a minimum total vent length of 16
equivalent feet could result in property damage and improper
product operation.
F. Longer Vent Runs
The maximum total equivalent length can be extended
by increasing the diameter of both the exhaust vent and
intake pipes equally. However, the transitions should begin
a minimum of 16 equivalent feet from the boiler. Transitions
should always be made in vertical sections of pipe to prevent
the condensate from pooling in the vent pipe.
The maximum equivalent length for increased diameter vent
pipes is 275 ft, which includes 16 ft from with boiler with a
transition total of 259 ft upsize piping for longer vent runs.
Figure 11 - Extended Vent Runs
Equivalent Feet
4"
6"
8"
3'
3'
3'
1'
1'
1'
0'
0'
0'
0'
0'
0'
1'
1'
1'
1'
1'
1'
1'
1'
1'
o
elbows, one 45
Standard
Vent Connection and
Maximum Total
Equivalent Length
4" (200')
6" (200')
Table 10 - Vent Run Transition
Total maximum equivalent length of increased diameter exhaust
vent and intake pipe must not exceed the lengths defined in this
manual. Failure to keep the total equivalent length below the
maximum lengths determined in this manual will result in faulty
boiler operation, substantial property damage, serious personal
injury, or death.
G. Exhaust Vent and Intake Pipe Installation
All joints of positive pressure vent systems must be sealed
completely to prevent leakage of flue products into the living
space. Failure to do so could result in property damage, serious
injury, or death.
1. Use only solid PVC, CPVC, or stainless steel pipe or a
Polypropylene vent system approved for use with Category IV
appliances.
o
FOAM CORE PIPING IS NOT APPROVED FOR EXHAUST VENT
APPLICATIONS. Foam core piping may be used on air inlet
piping only.
2. Remove all burrs and debris from joints and fittings.
3. When using PVC or CPVC pipe, all joints must be properly
cleaned, primed, and cemented. Use only cement and primer
approved for use with the pipe material. Cement must conform
to ASTM D2564 for PVC and ASTM F493 for CPVC pipe. NOTE:
DO NOT CEMENT POLYPROPYLENE PIPE.
4. Ensure the vent is located where it will not be exposed to
prevailing winds.
5. In all roof venting applications, exhaust discharge must point
away from the pitch of the roof.
6. If the exhaust vent is to be terminated in a walled off area
(such as a roof with a parapet wall), ensure the exhaust vent
terminates a minimum of 10' from nearest wall and extends level
with or above the top of the wall. This will ensure flue gas does
does not get trapped and possibly recirculated into the intake air
pipe, which could contaminate the combustion air.
7. To prevent water leakage, install adequate roof flashing where
the pipe enters the roof.
8. Do not locate vent over public walkways, driveways, or
parking lots. Condensate could drip and freeze, resulting in a slip
hazard or damage to vehicles and machinery.
9. Due to potential moisture build-up, sidewall venting may not
be the preferred venting option. To save time and cost, carefully
consider venting installation and location.
10. Horizontal lengths of exhaust vent must slope back towards
the boiler not less than ¼" per foot to allow condensate to drain
from the vent pipe.
11. The exhaust vent must terminate where vapors cannot make
accidental contact with people or pets, or damage shrubs or
plants.
12. In vacant chimney applications, install and seal a rain cap
Increased Vent Size
Reducing
and Maximum Total
Coupling
Equivalent Length
6" x 4"
6" (275')
8" x 6"
8" (275')
WHL-033 Rev. 1.29.16
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbmc**850

Table of Contents