Heat-N-Glo 6000CAMP Installer's Manual page 19

Table of Contents

Advertisement

For Vertical Runs - The vent system must be supported
every eight (8) feet (2.4m) above the fireplace flue outlet by
wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall
bracket to the framing members with nails or screws.
FLUE
OUTLET
1 INCH MIN.
(25.4mm)
Figure 24. Installing Support Brackets
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.
NOTE: Model DVK-01TRD does not need an exterior
firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through
either interior or exterior walls:
• Cut a 12-inch by 12-inch (305mm X 305mm) hole through
the wall.
NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.
WALL BRACKET
WALL STUD
8 FT. (2.4m)
• Position the firestops on both sides of the hole previ-
ously cut and secure the firestops with nails or screws.
• The heat shields of the firestops MUST BE placed to-
wards the top of the hole.
• Continue the vent run through the firestops.
NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.
Figure 25. 12" x 12" Hole and Vent Pipe
HEAT SHIELD
INTERIOR
FIRESTOP
Figure 26. Heat Shield, Interior & Exterior Firestops
21
12"
(305mm)
12"
(305mm)
1" (25.4 mm)
VENT PIPE
TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT
EXTERIOR
FIRESTOP