2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
●
areas where leakage of fl ammable gas may be expected.
●
places where large amounts of oil mist exist.
●
direct sunlight.
●
locations near heat sources which may affect the
performance of the unit.
●
locations where external air may enter the room directly. This
may cause "sweating" on the air discharge ports, causing
them to spray or drip.
●
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
●
installing the remote controller behind curtains or furniture.
●
locations where high-frequency emissions are generated.
DO:
●
select an appropriate position from which every corner of the
room can be uniformly cooled.
●
select a location where the ceiling is strong enough to
support the weight of the unit.
●
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
●
allow room for operation and maintenance as well as
unrestricted air fl ow around the unit.
●
install the unit within the maximum elevation difference above
or below the outdoor unit and within a total tubing length (L)
from the outdoor unit as detailed in the installation manual
packed with the outdoor unit.
●
allow room for mounting the remote controller about 3 ft. off
the fl oor, in an area that is not in direct sunlight nor in the
fl ow of cool air from the indoor unit.
●
The elevation (Low Silhouette Ducted, Slim Low Static
Ducted) between the bottom unit and the fl oor surface should
be at least 8 feet.
●
If the elevation (Low Silhouette Ducted, Slim Low Static
Ducted) between them is less than 8 feet, install a fi lter
(optional/fi eld supply) or a protective device (fi eld supply) not
to touch the electrical parts or fan with hands.
●
The air intake and outtake openings should be provided with
the same location of a room.
NOTE
Air delivery will be degraded if the distance from the fl oor
to the ceiling is greater than 10 ft.
VRF_Indoor_US.indb 9
VRF_Indoor_US.indb 9
Slim Low Static Ducted Type
Low Silhouette Ducted (High Static Pressure) Type
4-Way Cassette (60 × 60) Type
10 in.
10 in.
10 in.
Fig. 2-1
Shows Low Silhouette Ducted Type
and Slim Low Static Ducted Type
Fig. 2-2
Wall Mounted Type
Min.
6 in.
Front View
Fig. 2-3
Floor Standing, Concealed Floor Standing Type
min.
min.
3-15/16"
3-15/16"
min. 3.3 ft.
Horizontal view
Fig. 2-4
Ceiling Type
Ceiling
Min. 10 in.
Min. 10 in.
Front view
NOTE
The rear of the indoor unit can be installed fl ush against the wall.
Fig. 2-5
1-Way Cassette Type
Ceiling
Min. 2 in.
Wall
Obstacle
Fig. 2-6
9
3 ft.
3 ft.
3 ft.
3 ft.
Min.8 ft.
Min. 6 in.
Min.
6 in.
min. 3.3 ft.
Vertical view
Air
discharge
Wall
Air intake
Min. 2 ft.
Side view
Max. 10 in.
Obstacle
Air
discharge
Air
Wall
intake
Min. 2 in.
Side view