2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● Areas where leakage of flammable gas may be expected.
● Places where large amounts of oil mist exist.
● Direct sunlight.
● Locations near heat sources which may affect the
performance of the unit.
● Locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
● Locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● Installing the remote controller behind curtains or furniture.
● Locations where high-frequency emissions are generated.
DO:
● Select an appropriate position from which every corner of the
room can be uniformly cooled.
● Select a location where the ceiling is strong enough to
support the weight of the unit.
● Select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● Allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● Install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
manual packed with the outdoor unit.
● Allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
● If the indoor unit is installed on the ceiling where the
temperature or humidity inside is high (over 30°C/RH: 70%),
add insulating material to the surface of the unit to avoid dew
condensation.
Pana_indoor_F616337_Eng1.indd 6
Fig. 2-1
6