CAUTION
(4) When the check of drainage is complete, open the check pin (CHK)
and remount the insulator and drain cap onto the drain inspection port.

3-34. Increasing the Fan Speed

For Short Circuit Connection
The standard (before shipment) external static pressure is shown in the table below.
When using with a higher static pressure, it is necessary to change to the high static pressure mode.
External static pressure
Type
Standard (in.WG)
High static pressure (in.WG)
When using with high static pressure mode, set the indoor unit control board
as shown at right. Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confi rm that it is the indoor unit
control board.
(2) Connect the short circuit connector to the short circuit pin TP3 (2P:
Yellow) of the indoor unit control board.
In case of wired remote controller setting, do not use the short circuit connector.
For Wired Remote Controller
Press and hold the
longer.
"
," unit No. "
and settings data "
LCD display.
At this time, the indoor unit fan (or all indoor unit fans in the case of group
control) begins operating.
Press the temperature setting
"
".
Press the timer time
* For item codes and setting data, refer to the right table.
Press the
button.
(The display stops blinking and remains lit, and setting is completed.)
Press the
button to return to normal remote controller's display.
S-07MM1U6
0.16
HH
0.12
H
L
0.08
0.04
L
H
HH
0
177
353
Airflow (CFM)
S-12MM1U6
0.20
HH
0.16
H
0.12
L
0.08
H
HH
0.04
L
0
177
353
Airflow (CFM)
VRF_Indoor_US.indb 40
VRF_Indoor_US.indb 40
Be careful since the fan will
start when you short the pin
on the indoor control board.
7
9
0.04
0.06
0.06
0.12
0.12
0.16
,
and
buttons simultaneously for 4 seconds or
" (or "
" in the case of group control), item code "
" are displayed blinking on the remote controller's
/
buttons to select the item code
/
buttons to select the desired setting data.
S-09MM1U6
0.197
0.16
HH
0.12
H
L
0.08
H
0.04
L
HH
0
0
177
353
Airflow (CFM)
S-15MM1U6
0.24
0.20
0.197
HH
0.16
H
L
0.12
0.08
HH
HT
H
0.04
L
0
0
177
353
Airflow (CFM)
Water inlet
Eyelet cap
12
15
18
0.06
0.06
0.16
0.16
External static pressure's upper
0.197
limit in high static pressure mode
Standard external static
pressure's upper limit
0
Lower limit airflow
S-18MM1U6
0.24
HH
0.20
0.197
0.197
H
0.16
L
0.12
HH
0.08
H
L
0.04
0
0
0
353
530
Airflow (CFM)
40
Wiring port
Fig. 3-117
White Yellow Red
TP6
TP3 TP1
Indoor control board
2
,"
6
1
5 1
4
Item
code No.
Description
0000 Standard (setting at shipment)
0003 High static-pressure
Rated external static
HH
pressure in high static
pressure mode
H
Lower static pressure
L
in high static pressure
mode
HH
H
Rated external static
L
pressure at shipment
Upper limit airflow
Airflow (CFM)
3
2011/09/30 12:23:08
2011/09/30 12:23:08