(5) Before suspending the indoor unit, remove the 2 or 3 screws on the
latch of the air-intake grilles, open the grilles, and remove them by
pushing the claws of the hinges as shown in Fig. 3-135. Then remove
both side panels sliding them along the unit toward the front after
removing the 2 attachment screws. (Fig. 3-136)
(6) Carry out the preparation for suspending the indoor unit. The
suspension method varies depending on whether there is a suspended
ceiling or not. (Figs. 3-137 and 3-138)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each suspension bolt as
shown in Fig. 3-139.
b) Lift the indoor unit, and place it on the washers through the notches,
in order to fi x it in place. (Fig. 3-140)
c) Tighten the 2 hexagonal nuts on each suspension bolt to suspend the
indoor unit as shown in Fig. 3-141.
NOTE
The ceiling surface is not always level. Please confi rm that the indoor unit is
evenly suspended. For the installation to be correct, leave a clearance of
about 3/8" between the ceiling panel and the ceiling surface and fi ll the gap
with an appropriate insulation or fi ller material.
(8) If the tubing and wiring are to go towards the rear of the unit, make
holes in the wall. (Fig. 3-142)
(9) Measure the thickness of the wall from the inside to the outside and cut
PVC pipe at a slight angle to fi t. Insert the PVC pipe in the wall.
(Fig. 3-143)
NOTE
The hole should be made at a slight downward slant to
the outside.
VRF_Indoor_US.indb 46
VRF_Indoor_US.indb 46
Fig. 3-140
Indoor
Outdoor
side
side
Fig. 3-142
Slide toward
front side
Side panel
Unit
Unit
Washer
(supplied)
PVC pipe (locally purchased)
Cut at slight angle
Fig. 3-143
46
Fig. 3-136
Suspension bolt
(field supply)
Ceiling surface
Washer (supplied)
Double nut
Fixture
(field supply)
Fig. 3-137
Suspension bolt
(field supply)
Washer (field supply)
Washer (supplied)
Double nut
(field supply)
Fig. 3-138
Ceiling
surface
Nut
(field supply)
Suspension bolt
Fig. 3-139
Fig. 3-141
INSIDE
OUTSIDE
W all
PVC pipe
Slight
angle
2011/09/30 12:23:09
2011/09/30 12:23:09