Standard Operation Data (Reference Data); Cooling Only Operation - Mitsubishi Electric CMB-WP1016V-GA1 Service Handbook

2016
Hide thumbs Also See for CMB-WP1016V-GA1:
Table of Contents

Advertisement

[ VII Test Run Mode ]

[6] Standard Operation Data (Reference Data)

(1) Cooling only operation

Model name of HBC controller
No. of HBC controllers required
Ambient tem-
perature
Operating
Indoor unit
conditions
Piping
Amount of refrigerant
Electric current
Outdoor unit
Voltage
Compressor frequency
Electric current
HBC control-
Voltage
ler unit
Water pump command value [two units]
LEV opening
HBC controller
High pressure(63HS1)/
Pressure on
Low pressure(63LS)
the refrigerant
side
HBC controller PS1
Temp. on the
Outdoor unit
refrigerant
side
HBC controller LEV1/LEV2 inlet
Temp. on the
HBC controller
water side
Indoor unit
HWE1410A
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Fan speed
Main pipe
Branch pipe
Total water pipe length
LEV1
LEV2
LEV3
Discharge TH4
Heat exchanger outlet
TH3
Accumulator inlet TH5
Accumulator outlet
Compressor inlet
Compressor shell bot-
tom
Water heat exchanger
outlet TH32/TH33
Inlet
Outlet
- 92 -
Outdoor unit model
PURY-P200YLM-A1
CMB-WP108V-GA1
1
27°C/ 19°C
[81°F/ 66°F]
DB/WB
35°C/ -
[95°F/ -]
5
Unit
5
40/40/40/40/40
-
Hi
5 [17]
m
2.5 [9]
[ft]
12.5 [42]
kg
13.1 [29]
[lbs]
A
11.2
V
400
Hz
63
A
2.89
V
230
%
100
300
Pulse
300
80
2.83/ 0.97
MPa
[411/ 141]
[psi]
1.03 [150]
77 [171]
43 [110]
16 [61]
16 [61]
17 [63]
°C
28 [83]
[°F]
40 [104]
15 [59]
15 [59]
20 [68]
PURY-P250YLM-A1
1
27°C/ 19°C
[81°F/ 66°F]
35°C/ -
[95°F/ -]
6
6
40/40/40/40/40/50
Hi
5 [17]
2.5 [9]
15.0 [50]
13.3 [30]
15.9
400
86
2.89
230
100
300
300
80
3.04/ 0.93
[441/ 135]
1 [146]
86 [187]
46 [115]
15 [59]
14 [58]
15 [59]
36 [97]
43 [110]
15 [59]
15 [59]
20 [68]
GB