Functions And Factory Settings Of The Dipswitches - Mitsubishi Electric CMB-WP1016V-GA1 Service Handbook

2016
Hide thumbs Also See for CMB-WP1016V-GA1:
Table of Contents

Advertisement

[ VI Control ]
VI Control

[1] Functions and Factory Settings of the Dipswitches

1. Switch functions <HBC controller> (Control board)
Switch
1 - 3
Model setting
4
SVM1 ON fixed
5
control
SW3
Pressure sensor
6 - 7
backup
8
9
Heat recovery de-
10
frost
Debris removal run
1
mode
2
Test run air vent
3
mode after strainer
processing
Forced termination
4
of a test run
SW4
Water tightness
5
check
Operation function 1
6
of the valve block
7
8
9
10
Water supply SW
1
Air vent SW
2
3
Compatible with
4
SW5
antifreeze-liquid 1
Compatible with
5
antifreeze-liquid 2
6
7
8
HWE1410A
Function
R410A
-
Not available
Error codes are not sent to
outdoor units
-
-
Available
Not available
-
Not available
Not available
Not available
(When the switch is set from
ON to OFF, set the VB3 to the
specified opening for stop-
page.)
Not available
-
-
-
-
Not available
Not available
-
-
-
-
Function according to switch setting
OFF
-
Available
Error codes are sent to out-
door units.
-
-
Not available
Available
-
Available
Available
Available
Two water pumps ON (output
30%) one minute after setting
VB3 to 0 or 1600.
VB3=800
-
-
-
-
Available: VB=0 or 1600
Available
-
Refer to the Databook.
-
-
-
- 69 -
Switch setting tim-
ing
ON
Always leave this
-
switch to OFF.
-
Any time after be-
ing energized
Any time after be-
ing energized
-
-
Before being ener-
gized
Any time after be-
ing energized
-
Any time after be-
ing energized
Any time after be-
ing energized
Any time after be-
ing energized (only
when the control
mode is stopped)
Any time after be-
ing energized
-
-
-
-
Any time after be-
ing energized
Any time after be-
ing energized
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
GB