Standard Operation Data (Reference Data) - Mitsubishi Electric PFAV-P250VM-E Service Manual

Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents

Advertisement

[ IX Test Run Mode ]

[7] Standard Operation Data (Reference Data)

1. Single unit
(1) Cooling operation
Specifications
Ambient
tempera-
ture
Operating
conditions
Piping
Refrigerant charge
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC(LEV1)
ing
LEV2
High pressure (after O/S)/Low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10190
Indoor unit
Outdoor unit
Indoor
Outdoor
Main pipe
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
Compressor suction
Compressor shell bot-
tom
LEV inlet
Heat exchanger outlet
PFAV-P250VM-E
model
PUHY-P250YJM-A
model
27°C/19°C
[81°F/66°F]
DB/WB
35°C/- [95°F/-]
m[ft]
7.5 [24-1/4]
kg
11.5 [25-6]
[lbs-oz]
A
12.3
V
400
Hz
65
387
Pulse
100
2100
MPa
3.11/0.86 [451/125]
[psi]
85 [185]
44 [111]
7 [45]
7 [45]
°C [°F]
24 [75]
19 [66]
38 [100]
19 [66]
6 [43]
- 117 -
PFAV-P300VM-E-F
PUHY-P250YJM-A
33°C/28°C
[91°F/82°F]
33°C/- [91°F/-]
7.5 [24-1/4]
11.5 [25-6]
11.9
400
65
770
120
2100
3.31/1.00 [480/145]
85 [185]
43 [109]
13 [55]
13 [55]
28 [82]
22 [72]
40 [104]
27 [81]
13 [55]
GB