Mitsubishi Electric CMB-WP1016V-GA1 Service Handbook page 197

2016
Hide thumbs Also See for CMB-WP1016V-GA1:
Table of Contents

Advertisement

[ VIII Troubleshooting ]
7. Strainer
Operation procedures
(1) Unscrew the four fixing screws from the
service panel on the right to remove it
(when servicing the strainer on the
Heating-main side water-pump).
(2) Unscrew the four fixing screws from the
service panel on the left to remove it
(when servicing the strainer on the Cool-
ing-main side water-pump).
(3) Unscrew the two screws on either side
of the control box. (Applicable to CMB-
WP108V-GA1 only)
(4) Slide the control box to the left until the
strainer is visible (Approx. 150 mm).
(Applicable to CMB-WP108V-GA1 only)
(5) Using the supplied spanner plate, open
the cover at the bottom of the strainer.
(6) Pull out the strainer downward, and re-
place it.
*Fully tighten the cover at the bottom of
the strainer. Failing to do so may cause
a water leakage.
HWE1410A
Illustrations
Strainer body
Service panel (left)
Service panel (right)
Control box
- 188 -
Strainer body
Slide the control box.
Supplied spanner plate
(1.6T)
Strainer
Operation
location
In ceiling
space
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmb-wp108v-ga1Cmb-wp108v-gb1Cmb-wp1016v-gb1

Table of Contents