Mitsubishi Electric CMB-WP1016V-GA1 Service Handbook page 188

2016
Hide thumbs Also See for CMB-WP1016V-GA1:
Table of Contents

Advertisement

[ VIII Troubleshooting ]
3) Opening and closing of the valve
Water pump
2. Water pump
Check the connector and make sure that it is connected properly.
Check the driving power supply, control power supply for the pumps internal board, and check the control signal voltage by
connecting each voltage to ground. (Control signal voltage will be 0V when stopped and 6V when running at 100%)
If these are voltages are not correct then investigate the HBC pump power supply board.
If the supply voltages are correct, and the control signal is being sent and the pump will still not operate the likely causes are:
Internal pump control board failure - replace pump. (Note: The internal pump control board is usually damaged when remov-
ing and replacing the connector with the power supply turned on. Always remove the pump connector with the power supply
turned off.)
Coil failure - replace pump. If the windings have been damaged the pump will require replacing.
Internal mechanical failure such as bearing failure, turbine failure, magnet degradation. This will require pump replacement.
Before replacement the causes must be investigated and resolved. The pump shaft bearings and magnets can be easily dam-
aged by overheating due to dry running or water system blockage. Check the strainer for blockage, investigate the water
circuit for blockage and or foreign material, and that there is no air in the system or an uncontrolled leak.
Driving power
supply,
±
DC268V
Control power
(internal pump
board)
±
DC15V
10%
Control signal,
0-6V, 6V=100%
RPM pulse signal:
4 pulses per revolution
Ouput duty about 67%
Open collector type
5mA current
Max voltage: 50V
HWE1410A
Cooling
Closing
the valve
Opening
the valve
0
700
10%
Heating
Opening
the valve
800
900
Number of pulses
VDD (White)
GND (Black)
VCC (Red)
VSP (Brown)
FG (Blue)
- 179 -
Closing
the valve
1600
6
5
4
Pump
3
2
1
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmb-wp108v-ga1Cmb-wp108v-gb1Cmb-wp1016v-gb1

Table of Contents