Standard Operation Data (Reference Data) - Mitsubishi Electric PURY-P72TYJMU-A Service Handbook

Table of Contents

Advertisement

[ VIII Test Run Mode ]

[7] Standard Operation Data (Reference Data)

1. Single unit
(1) Cooling only operation
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0913A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 177 -
Outdoor unit model
PURY-P72TJMU-A
CMB-P104NU-G
26.7°C/19.4°C
[80 °F/67 °F]
35°C/í
[95 °F/í]
3
Unit
3
-
24/24/24
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
35
[114-13/16"]
-
Hi
kg
19.1 [42]
A
15.7
V
230
Hz
43
180/200/220
Pulse
2000/í/180
2.65/0.92
[384/133]
MPa
[psi]
2.59/2.59
[375/375]
76 [169]
41 [106]
14 [57]
°C
14 [57]
[°F]
23 [73]
34 [93]
24 [75]
12 [54]
PURY-P96TJMU-A
CMB-P104NU-G
26.7°C/19.4°C
[80 °F/67 °F]
35°C/í
[95 °F/í]
2
2
48/48
5 [16-3/8"]
10 [32-3/4"]
25 [82]
Hi
21.3 [47]
21.7
230
61
387/387
2000/í/170
2.78/0.90
[403/131]
2.70/2.70
[392/392]
87 [189]
41 [106]
8 [46]
8 [46]
19 [66]
40 [104]
19 [66]
6 [43]
GB