[ VII Test Run Mode ]
Model name of HBC controller
No. of HBC controllers required
Ambient
temperature
Operating
Indoor unit
conditions
Piping
Amount of refrigerant
Electric current
Outdoor unit
Voltage
Compressor frequency
Electric current
HBC control-
Voltage
ler unit
Water pump command value [two
units]
HBC con-
LEV opening
troller
High pressure(63HS1)/
Pressure on
Low pressure(63LS)
the refrigerant
side
HBC controller PS1
Outdoor unit
Temp. on the
refrigerant
side
HBC con-
troller
Temp. on the
HBC con-
water side
troller
Indoor unit
HWE1410A
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Fan speed
Main pipe
Branch pipe
Total water pipe length
LEV1
LEV2
LEV3
Discharge TH4
Heat exchanger outlet
TH3
Accumulator inlet TH5
Accumulator outlet
Compressor inlet
Compressor shell bot-
tom
LEV1/LEV2 inlet
Water heat exchanger
outlet TH32/TH33
Inlet
Outlet
PURY-P300YLM-A1
1
27°C/ 19°C
[81°F/ 66°F]
DB/WB
35°C/ -
[95°F/ -]
7
Unit
7
40/40/40/40/40/50/50
-
Hi
5 [17]
m
2.5 [9]
[ft]
17.5 [58]
kg
14.1 [32]
[lbs]
A
21.3
V
400
Hz
79
A
2.89
V
230
100
%
337
Pulse
337
80
2.95/ 0.87
MPa
[428/ 126]
[psi]
0.96 [140]
87 [189]
44 [112]
13 [56]
12 [54]
13 [56]
°C
35 [95]
[°F]
40 [104]
14 [58]
14 [58]
20 [68]
- 93 -
Outdoor unit model
PURY-P350YLM-A1
CMB-WP108V-GA1
1
27°C/ 19°C
[81°F/ 66°F]
35°C/ -
[95°F/ -]
9
9
40/40/40/40/40/40/40/40/40
Hi
5 [17]
2.5 [9]
22.5 [74]
14.1 [32]
28.7
400
100
2.89
230
100
468
468
80
3.15/ 0.83
[457/ 120]
0.94 [137]
95 [203]
46 [115]
12 [54]
11 [52]
12 [54]
34 [94]
39 [103]
14 [58]
14 [58]
21 [70]