Room sensors

Advertisement

Ordering

Equipment combinations

Mode of operation

Relative humidity
Temperature
Simulated passive
output signal
Sensing elements,
simulated
Legend

Mechanical design

2/6
Siemens Building Technologies
HVAC Products
When ordering, please give name and type reference.
All systems or devices capable of acquiring and handling the sensor's DC 0...10 V ,
LG-Ni 1000 or T1 output signal.
When using the passive sensors for averaging, we recommend to use the SEZ220
signal converter (refer to Data Sheet N5146).
The sensor acquires the relative humidity in the room via its capacitive humidity sens-
ing element whose electrical capacitance changes as a function of the relative humidity.
The electronic measuring circuit converts the sensor's signal to a continuous
DC 0...10 V signal, which corresponds to 0...100 % relative humidity.
The sensor acquires the temperature in the room via its sensing element whose electri-
cal resistance changes as a function of the temperature.
Depending on the type of sensor, this change in resistance is converted either to an
active DC 0...10 V output signal (
simulated passive LG-Ni 1000 or T1 output signal.
The measuring current from systems / devices für acquiring the electrical resistance of
the passive sensor differs greatly and impacts self-heating of the temperature sensing
element at the end of the measuring probe. To compensate the impact, the passive
output signal is simulated with an electronic circuit.
Characteristic LG-Ni 1000
R [Ω]
1400
1200
1000
800
600
−50
−40 −30 −20 −10
0
10 20 30 40 50 60 70 80
R
Resistance value in Ohm
ϑ
Temperature in degrees Celsius
The units have been designed for wall mounting. They are suitable for use with most
commercially available recessed conduit boxes. The cables can be introduced from the
rear (concealed wiring) or from below or above (surface-run wires) through knock-out
openings.
The units consist of two major sections: Casing and baseplate. Both snap together but
can be detached again.
The measuring circuit, the sensing elements and the setting element are located on the
printed circuit board inside the casing.
The baseplate carries the connecting terminals.
Room sensors QFA20...
0... 50 °C or – 35...+ 35 °C) or is provided as a
Characteristic T1 (PTC)
R [Ω]
3200
3000
2800
2600
2400
2200
2000
1800
1600
ϑ
1400
[°C]
−40 −30 −20 −10
[°C]
0
10 20 30 40 50 60 70 80
CE1N1857en