Pipe Insulation - Panasonic WH-SXH09D0E8 Service Manual

Air-to-water heatpump indoor unit outdoor unit
Hide thumbs Also See for WH-SXH09D0E8:
Table of Contents

Advertisement

3
Secure the cable onto the control board with the holder (clamper).
4
Select required direction and apply protective bushing provided in accessories to protect cables from sharp
edges.
5
Once all wiring work has been completed, tie the cable and cord together with the binding strap so that
they do not touch other parts such as the compressor and bare copper pipes.
6
Install back the control board cover.
11.4.4.1
Wire Stripping and Connecting Requirement
Same as indoor requirement. For details please refer the diagram on AIR-TO-WATER HEATPUMP INDOOR
UNIT, section 11.3.4 (CONNECT THE CABLE TO THE INDOOR UNIT).
CAUTION
For three phase model never operate the unit by pressing the electromagnetic switch.
Never correct the phase by switching over any of the wires inside the unit.
11.4.5

Pipe Insulation

1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
11.4.6
Outdoor Unit Drain Water
Water will drip from the basepan hole area during defrost function.
To avoid water dripping, do not stand or place objects at this area.
30