Panasonic WH-SXH09D0E8 Service Manual page 63

Air-to-water heatpump indoor unit outdoor unit
Hide thumbs Also See for WH-SXH09D0E8:
Table of Contents

Advertisement

16.5.17 IPM Overheating (F22)
Malfunction Decision Conditions:
During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature
sensor.
Malfunction Caused:
1
Faulty outdoor unit fan motor.
2
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 4 times in 30 minutes.
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ux09dn8

Table of Contents