16.5.18 Output Over Current Detection (F23)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor DC current is above 33.4 ± 5.0A is detected by the IPM
DC Peak sensing circuitry in the outdoor unit PCB (main).
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty compressor.
Abnormality Judgment:
Continue for 7 times.
64