WIRING DIRECTIONS

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS OR SENSORS.
Each WattStopper BZ series power
pack can supply power for 4 UT-305
sensors. When using more sensors
than this, multiple power packs are
required.
Refer to the wiring diagram on the next
page for the following procedures:
Connect the low voltage:
• RED wire (+24VDC) from power pack
to the +24V terminal on the sensor.
• BLACK wire (Return) from power
pack to Common terminal on the
sensor.
Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY–connect:
• B LUE wire from power pack to Control Out terminal on sensor.
To add a MANUAL SWITCH such as the LVS-1 Momentary Toggle Switch, or RS2-3
Low Voltage Momentary Switch to the above applications–connect:
• Wire from one side of switch to Common terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
CAUTION
Call 800.879.8585 for Technical Support
03624r2
UT-305
Ultrasonic
Occupancy Sensor
40kHz Ultrasonic
LISTED
+24VDC/VAC
88T9
Connect to Watt Stopper
Appliance
Control
Class 2 Power Packs
For Indoor Use Only
U.S.Patents:
Control Out.
5,640,113
Patent Pending
Man. Switch
+24V
Common
www.wattstopper.com
800.879.8585