Outdoor Unit Electronic Expansion Valve - Fujitsu AU*G36LRLA Service Instruction

3 phase type room air conditioner
Hide thumbs Also See for AU*G36LRLA:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 3

Outdoor unit Electronic Expansion Valve

( EEV )
Check Point 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
RED
BROWN
BLUE
CN17
ORANGE
YELLOW
WHITE
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
White - Red
Yellow - Brown
46
Orange - Red
Blue - Brown
If resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing operation of valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot gas
Pipe (In)
Check Point 6 : Check strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in
but if there is a difference as shown in
Pipe (In)
EXPANSION
VALVE COIL
EV
Resistance value
4
at 20°C
Pipe (Out)
, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
Check Point 3 : Check noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
Check Point 4 : Check voltage from Main PCB.
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
12V
RED
1
1
BROWN
2
2
BLUE
3
3
CN17
ORANGE
4
4
YELLOW
5
5
WHITE
6
6
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot gas
Pipe (In)
Pipe (In)
02-41
EV
Pipe (Out)
,
Pipe (Out)
DC