1 -22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes more than 105°C, the compressor frequency -10rps,
and it continues the frequency -10rps every 2 minutes until the temperature becomes less than 105°C.
When the discharge temperature becomes less than 100°C,
the control of the compressor frequency is released.
When the discharge temperature becomes more than 115°C,
the compressor is stopped.
2. COMPRESSOR TEMPERATURE PROTECTION CONTROL
When the compressor temperature thermistor detects more than 110°C, the compressor is stopped at once.
Cooling/ Dry
Setting temp.+1°C
Setting temp.-1°C
Heating
10°C
Auto
Economy
Operate as normal
01-28
Heating
(Fig 17 : Discharge temperature control)
Discharge
temperature
115°C
105°C
100°C
Compressor stop
-10rps every 2 minutes
Hold
Release of protection