Forced Cooling Operation; Compressor Stop Control; Fresh Air Control; External Electrical Heater Control - Fujitsu AU*G36LRLA Service Instruction

3 phase type room air conditioner
Hide thumbs Also See for AU*G36LRLA:
Table of Contents

Advertisement

1-23. FORCED COOLING OPERATION (When using the Wireless RC)
The FORCED COOLING OPERATION starts up when MANUAL / AUTO button is pressed more than 10 seconds.
During the FORCED COOLING OPERATION, it keeps operation regardless of detection
value of room temperature sensor.
Operation LED and Timer LED blinks simultaneously while the unit is on the FORCED COOLING OPERATION.
It is released after 60 minutes from starting time.

1-24. COMPRESSOR STOP CONTROL

When the detection value of outdoor temperature sensor is lower than temperature
in the table below, the compressor is stopped.
(Table 14 : Operation temperature of compressor stop control)
Operation
temperature
1-25. FRESH AIR CONTROL (For AU/ AR type)
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation
as shown in Figure 20.
(Fig 20 : Fresh Air control)
Operation
Fan motor
(Indoor unit)
Stop
Operation
Fan motor
(for Fresh Air)
Stop
1-26. EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)
The External Electrical Heater is operated as shown in Figure 21.
(Fig 21 : External Electrical Heater control)
Ts -3°C
Ts -12°C
When the room
temperature drops
Temperature
Cooling
Heating
- 20°C
When the room
temperature rises
Heater : OFF
Heater : ON
Heater : OFF
01-31
Ts : Setting temperature
When the compressor stop,
External Electrical Heater is OFF.
Ts -1°C
It operates only in Heating mode
and when the indoor fan operates.
Ts -10°C
(However, S-Low is excluded)