Vent Configurations with Horizontal Termination (EmberFyre Burner only)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
NOTE: With no vertical rise, LP installations have a maximum run of 2 feet (0.6m); NG installations have a
maximum run of 4 feet (1.2m).
21' max (6.4m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(
Exhaust Restrictor #4
Intake Restrictor #4
Diffuser Position #2 (OPEN)
Exhaust Restrictor #1
Intake Restrictor #1
Diffuser Position #1 (CLOSED)
2' LP/4' NG Maximum
H2
.
H1
for qualified installers only)
Exhaust Restrictor # 5
Exhaust Restrictor #3
Intake Restrictor #3
Diffuser Position #2 (OPEN)
Exhaust Restrictor #2
Intake Restrictor #3
Diffuser Position #2 (OPEN)
Horizontal length (max. 24') is calculated
by adding both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a vertical elbow.
4141013
21
21' max (6.4m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01414