Cycle Time/24 Hour Ice Production/Refrigerant Pressure Charts; Q200 Series - Manitowoc QR0320A Service Manual

Q series
Table of Contents

Advertisement

Section 7
Cycle Time/24 Hour Ice Production/
Refrigerant Pressure Charts

Q200 SERIES

Self-Contained Air-Cooled
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Entering
Water Temperature °F/°C
Condenser
50/10.0
°F/°C
70/21.1
11.5-13.5
80/26.7
13.8-16.1
90/32.2
16.1-18.7
100/37.8
19.8-23.0
Times in minutes
24 Hour Ice Production
Air Temp.
Water Temperature °F/°C
Entering
Condenser
50/10.0
°F/°C
70/21.1
270
80/26.7
230
90/32.2
200
100/37.8
165
Based on average ice slab weight of 2.44 - 2.81 lb
Regular cube derate is 7%
Operating Pressures
Freeze Cycle
Air Temp.
Entering
Discharge
Condenser
Pressure
°F/°C
PSIG
50/10.0
195-260
70/21.1
195-260
80/26.7
210-270
90/32.2
240-290
100/37.8
270-330
110/43.3
310-390
Suction pressure drops gradually throughout the freeze cycle
Part No. 80-1100-3
Freeze Time
70/21.1
90/32.2
13.8-16.1
15.2-17.8
15.6-18.2
17.0-19.8
18.6-21.6
20.5-23.8
23.6-27.4
25.5-29.6
70/21.1
90/32.2
230
205
175
140
Harvest Cycle
Suction
Discharge
Pressure
Pressure
Pressure
PSIG
PSIG
60-28
120-190
60-28
120-190
65-28
160-190
70-30
190-210
70-35
220-240
85-40
250-270
Q200 SERIES
Self-Contained Water-Cooled
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Around Ice
Machine
°F/°C
Harvest
70/21.1
Time
80/26.7
90/32.2
100/37.8
1.0-2.5
Times in minutes
24 Hour Ice Production
Air Temp.
Around Ice
Machine
°F/°C
70/21.1
80/26.7
90/32.2
210
100/37.8
190
Based on average ice slab weight of 2.44 - 2.81 lb
160
Regular cube derate is 7%
130
Condenser
Water
Consumption
Gal/24 hours
Suction
Water regulating valve set to maintain 230 PSIG discharge pressure
PSIG
Operating Pressures
85-110
Air Temp.
85-110
Around Ice
90-110
Machine
100-120
°F/°C
120-140
50/10.0
120-150
70/21.1
80/26.7
90/32.2
100/37.8
110/43.3
Suction pressure drops gradually throughout the freeze cycle
Refrigeration System
Freeze Time
Water Temperature °F/°C
50/10.0
70/21.1
11.5-13.5
12.8-15.0
12.0-14.1
13.5-15.7
12.6-14.7
14.1-16.5
13.1-15.4
14.8-17.3
Water Temperature °F/°C
50/10.0
70/21.1
270
245
260
235
250
225
240
215
90/32.2 Air Temperature
Around Ice Machine
Water Temperature °F/°C
50/10.0
70/21.1
240
480
Freeze Cycle
Discharge
Suction
Discharge
Pressure
Pressure
Pressure
PSIG
PSIG
225-235
60-28
225-235
60-28
225-240
60-28
225-245
65-30
225-250
70-32
225-260
75-34
Harvest
Time
90/32.2
14.5-16.9
15.2-17.8
1-2.5
16.1-18.7
17.0-19.8
90/32.2
220
210
200
190
90/32.2
2100
Harvest Cycle
Suction
Pressure
PSIG
PSIG
170-200
90-110
170-200
90-110
175-205
90-110
175-205
90-115
180-210
90-115
185-215
90-120
7-33