User Settings - REMEHA W40 Installation And Maintenance Instructions Manual

High-efficiency condensing boiler for free standing (frame mounted) or wall mounted installation
Table of Contents

Advertisement

6.4.10 User settings

The user can set the following parameters to the
required values.
1. Flow temperature (basic setting 80˚C).
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- The set value 8 0 is shown in the temperature
display.
- Now set the required flow temperature, using the
' '- and ' '-keys.
Code
Description
1.
7 0
Required flow temperature
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'mode'-key until the digit without dot
appears in the 'code'-display.
2. Pump switching (basic setting: pump continues to
operate for 5 minutes)
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- Press the 'step'-key until the digit 2. appears in the
'code'-display.
- Set the required value, using the ' '- and ' '-keys.
Code
Description
2.
0 0
Pump continues to operate for 10 sec.
2.
X X Pump continues to operate for
1 - 15 min. (example:
2.
9 9
Continuous pump operation
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'mode'-key until the digit without dot
appears in the 'code'-display.
3. D.H.W. setting (basic setting 65˚C). Only with sensor.
Operation is as follows:
Imagine: the setpoint for D.H.W. temperature has been
preset at 65°C, the D.H.W. cut-in temperature differen-
tial at 5°C, and the maximum flow temperature during
D.H.W. operation at 80°C (factory settings).
The appliance will modulate at the preset maximum flow
temperature during D.H.W. operation, and will shut down
at a D.H.W. temperature of 70°C (preset value +5°C).
The appliance will cut back in at a D.H.W. temperature
of 65°C (preset D.H.W. temperature
+5°C - D.H.W. cut-in temperature differential).
Both the D.H.W. cut-in differential and the maximum flow
temperature during D.H.W. operation can only be set via
the service menu (para. 10.3.9 and 10.3.10).
X X
= 05)
16
remeha W40/60-m ECO
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- Press the 'step'-key until the digit 3. appears in the
'code'-display.
- Set the required value, using the ' '- and ' '-keys.
Code
Description
3.
6 5
required temperature
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'reset'-key to return into the operating
mode.