Vii) Specifications - NewMar PT-24-45W Bb8Db2Cc8C9B8A4Bb2Bbe763F

Three stage smart charger
Hide thumbs Also See for PT-24-45W:
Table of Contents

Advertisement

Condition
B. Charger continues to
charge at 3 amps or more
does not taper back in
charge.
C. Front panel status Indicator
is not lit and there is no
indication of charger output.
D. Charger repeatedly trips
input circuit breaker with no
batteries connected.
VII) Specifications
Input
Model
VAC±10% 50-60 Hz
PT-24-45W
230
PT-24-60W
230
PT-24-95W
230
PT-32-25W
115
PT-32-70W
230
* P.L. = Maximum amps at Power Limit
** F.V. = Maximum amps at Full (Float) Voltage—See OUTPUT VOLTAGES below
CASE SIZE
Inches: 19.7" H* x 12.1" W x 5.2" D*
*Add 1" (2.54 cm) to height and depth with drip shield installed
OUTPUT VOLTAGES
(without Temperature Compensation option installed):
Charge @ 50% load
Gel-Cell
28.0V D.C.
Lead Acid
28.4V D.C.
TEMPERATURE COMPENSATION:
14
P.O. Box 1306, Newport Beach, California 92663 • Phone: 714-751-0488 • Fax: 714-957-1621 • E-Mail: techservice@newmarpower.com
Possible Cause
1. D.C. load drawing current from batteries
(not a problem condition.)
2. bad cell in one of the batteries to which
charger is connected.
1. Charger is not receiving A.C. input voltage
or is connected to incorrect A.C. voltage.
2. Reverse polarity connection or direct short
across output terminals has caused failure.
Internal short.
Max
Output
Amps
Max Amps @ P.L.*
8
45
15
60
17
95
15
27
17
70
Centimeters: 50.0 H x 30.7 W x 13.2 D
24 VOLT MODELS
Float @ .5 amp load
27.2V D.C.
26.8V D.C.
-5 mV per cell per ºC
www.newmarpower.com
Solution
1. To confirm charger will output minimal amperage to
fully charged batteries, shut off all d.c. loads or turn off
main battery switch to d.c. distribution panel.
2. Check for shorted cell in all flooded type batteries
- see Battery Care Tips section. Refer to manufacturer for
testing of maintenance-free batteries.
1. Confirm charger model is compatible with 115V or
230V A.C. voltage being applied. Check for proper
input voltage with A.C. voltmeter. Check input wiring
connections.
2. Refer to factory contact information in section XI.
Refer to factory contact information in section XI.
Output
Banks
Max Amps @ F.V.**
38
3
52
3
3
24
3
3
32 VOLT MODLES
Charge @ 50% load
Float @ .5 amp load
37.3V D.C.
37.8V D.C.
Weight
Capacity
(Amp-Hour)
Lbs.
Kg.
90-450
12.2
5.6
120-600
20
9.1
180-950
20
9.1
50-300
12.2
5.6
140-700
20
9.1
36.2V D.C.