21. ACTIVATING THE FLUE SWEEP FUNCTION
Proceed as follows to activate the flue sweep function before measuring combustion efficiency and fume composition.
1) Turn knobs 6 and 7 (figure 1) fully anti-clockwise to their minimum positions as shown in figure 18A.
2) Starting in this position, quickly turn control knob 7 twice consecutively clockwise through about
in figure 18B.
NOTE: In FLUE SWEEP mode, LEDs 2 and 3 (figure 1) flash alternately and the display alternates the message
"SF" and the boiler output temperature about every five seconds (figure 19).
IMPORTANT: In FLUE SWEEP mode, do not turn knob 6 from its initial position or you will enter "calibration" mode in-
stead (see section 16.1).
3) Flue sweep mode remains active for 20 minutes. To exit FLUE SWEEP mode before this time, simply turn knob 7 (figure 1).
The function also stops if the central heating MAX. SETPOINT temperature is reached (see section 16.1 point 4).
22. OUTPUT / PUMP HEAD PERFORMANCES
This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The air vent valve
incorporated in the pump allows quick venting of the heating system.
PRIME HT 1.280 - HT 330
Graph 4
PRIME HT 1.240 - HT 280 - HT 240
Graph 4.1
WATER FLOW RATE (l/h)
WATER FLOW RATE (l/h)