REPLACEMENT OF PARTS
NOTE:
16.1
Removal of the syphon assembly will give access
to Auto air vent.
To release the syphon from the sump connection,
pull towards you (A).
Disconnect the discharge hose (B) at the
plumbing manifold.
Remove the complete syphon assembly
16. Diverter valve motor (if fitted)
Ensure the appliance is in service mode
(there is no need to drain the appliance).
Disconnect the electrical connector from the
diverter valve motor.
Remove diverter valve cover if fitted.
19.1 Pull the motor assembly (C) towards you. The
17.1
assembly will slide free from the valve.
To refit, follow the above in reverse.
D
17. Diverter valve (if fitted)
Ensure the appliance has been fully drained .
Disconnect the electrical connector from the
diverter valve motor.
Undo the two screws holding the valve to the
plastic housing.
Remove diverter valve cover if fitted.
17.1 Withdraw the valve (D) and clean the valve
chamber if necessary.
To refit, follow the above in reverse. Ensure
any seals that have been disturbed are
renewed.
18. Auto air vent
Ensure the appliance has been fully drained .
18.1 Use a screwdriver or similar to rotate the air
vent anticlockwise.
18.2 Lift the air vent (E) out of the housing and
remove.
To refit, follow the above in reverse.
18.2
.
REPLACEMENT OF PARTS
49