Temperature
Offset After
P ower
Cycle
To compensate
for internal
heat build-up
from the electronics
in the thermostat,
the thermostat
will add an offset to the actual temperature
that it measures.
If the
thermostat
power is cycled quickly,
one can witness
an immediate
increase
in the
actual temperature
displayed
due to this added offset. The thermostat
display
will
return to the actual room temperature
after several minutes
of operation.
TROUBLESHOOTING
If the display
module
doesn't
power
up after power
is applied,
check the Rc/Rh
and C terminals
for 24VAC.
If 24VAC is present,
check the voltage
between
Vg
and V+. This voltage
will be approximately
12-20VDC.
If voltage
is present,
check the polarity
to make sure it is wired correctly.
The display
will not power
up if polarity is reversed.
If dashes appear for Option
01 in config and during reboot,
the problem
could be
the red pigtail being wired to Rc or Rh and the black pigtail being wired to C. If
so, remove
the two-wire
pigtail and connect
to the V+ and Vg terminals.
Error
Codes
....
If AC/HP
Control
cannot
properly
read room temperature,
display
will
indicate
"--"
and all outputs
(except
fan, if on) will turn off. In the case where
the installer
has selected
to average the local sensor and the remote
room sensor,
the AC/HP
display
will alternate
between
"--"
for the failed
sensor
and the
temperature
sensed
by the working
sensor
every
10 seconds.
The control
will
operate
from the temperature
sensed by the working
sensor.
E1
-
If the
Display
Module
and
the
Equipment
Control
Module
cannot
communicate
via two-wire
connection,
an El will be displayed.
E2 - There is no E2 error message.
45