Three-Minute
Minimum
on Time
In normal operation,
when a stage turns on, it will not turn off for a minimum
of
3 minutes.
If the setpoint
is changed,
this timer
is canceled,
allowing
the
equipment
to turn off immediately
when the demand
is removed.
Heat/Cool
Setpoints
(Desired
Temperature)
A minimum
difference
of 1 _ and maximum
of 6 _ is enforced
between
heating
and cooling
desired
temperatures.
This is done by allowing
1 setting
to "push"
the
other,
to
maintain
this
difference.
This
difference
is
adjustable
via
Configuration
Option
11.
Equipment
On Indicators
When cooling
equipment
is on, a COOL
ON icon is displayed.
While
cooling
equipment
operation
is delayed
by the timeguard
or cycle timer,
COOL
ON will
flash. The same is true for HEAT ON.
When the W is energized
in a heat pump,
the auxiliary
heat on icon will be
displayed.
Auto Changeover
When
auto changeover
mode
is selected,
a change
from
heat to cool (or vice
versa) will not occur until an opposite
mode demand
has existed
for 20 minutes.
If setpoint
is changed,
20-minute
requirement
is deleted.
Emergency
Heat Mode
When
AC/HP
Control
is configured
as a heat pump
and emergency
heat is
selected,
all Y signals
are locked
out, and W becomes
energized
upon a call for
heat.