Class 5 Status Codes - Fronius Primo 3.8-1 208-240 Operating Instructions Manual

Inverter for grid-connected photovoltaic systems
Hide thumbs Also See for Primo 3.8-1 208-240:
Table of Contents

Advertisement

Available languages

Available languages

Code
Description
474
RCMU sensor faulty
Solar module ground, insula-
475
tion error (connection between
solar module and ground)
Supply voltage for driver too
476
low
Function incompatibility (one
or more PC boards in the in-
480,
verter are not compatible with
481
each other, e.g.,after PC board
replacement)
Commissioning is not com-
482
plete
Voltage U
DCfix
483
is outside of valid range
485
CAN transmission buffer is full
Class 5 Status
Class 5 status codes generally do not impair grid power feed operation, but can lead to lim-
Codes
itations in grid power feed operation. They will be displayed until the status code is ac-
knowledged by pressing a key (the inverter, however, continues working normally in the
background).
Code
Description
Insulation error on the solar
502
modules
No feed-in within the last 24
509
hours
515
No internal communication
with filter
516
Communication with memory
unit not possible
46
Details
Inverter does not feed energy
into the grid.
Inverter does not feed energy
into the grid.
Inverter does not feed energy
into the grid.
for MPP2 string
Inverter does not feed energy
into the grid.
Inverter does not feed energy
into the grid.
Details
Warning message is shown on
the display.
Warning message is shown on
the display.
Warning message on the dis-
play
Warning message of memory
unit
Rectification
If this status code keeps recur-
ring, contact your system in-
staller.
Update inverter firmware; *)
Reset AC (switch automatic
circuit breaker on and off), car-
ry out full commissioning.
Check MPP settings;
If status code persists:
contact a Fronius-trained ser-
vice technician.
Carry out AC reset (switch au-
tomatic circuit breaker off and
on);
If status code persists:
contact a Fronius-trained ser-
vice technician.
Rectification
If this status code keeps recur-
ring, contact your system in-
staller.
Acknowledge status code;
check if all conditions for fault-
free grid power feed operation
are fulfilled (e.g., if the solar
modules are covered with
snow).
If the status code persists: ob-
serve further status codes.
If status code persists: Contact
a Fronius-trained service tech-
nician

Hide quick links:

Advertisement

Table of Contents
loading