Lenovo RT1.5kVA Installation And User Manual page 59

2u rack or tower ups
Hide thumbs Also See for RT1.5kVA:
Table of Contents

Advertisement

AC Output power
50/60Hz, 1ph;
200VAC, 1550VA,
1100W, 7.5A;
208VAC, 1550VA,
1100W, 7.3A;
220VAC, 1550VA,
1100W, 6.9A;
230VAC, 1550VA,
1100W, 6.6A;
240VAC, 1550VA,
1100W, 6.3A
Output on battery
power
v Voltage
v Frequency
Battery (sealed lead
acid, maintenance
free)
v Standard
v Additional
modules possible
(up to 4 EBMs)
Environment
(1) Adjustable to 200/208/220/230/240 V (23 % derating at 200 V, 10 % derating at 208 V on 2.2 kV A, and 17 % derating at 200 V
on 3 kV A).
(2) 5594-2BX: 2 strings, each 4 x 12 V / 9 Ah.
(3) 5594-3BX: 2 strings, each 6 x 12 V / 9 Ah.
5594-1KX
5594-2KX
50/60Hz, 1ph;
200VAC, 1700VA,
1530W, 8.5A;
208VAC, 1980VA,
1780W, 9.5A;
220VAC, 2200VA,
1980W, 10.0A;
230VAC, 2200VA,
1980W, 9.6A;
240VAC, 2200VA,
1980W, 9.2A
230 V (-10/+6 %)
50/60 Hz ±0.1 Hz
4 x 12 V
4 x 12 V
7.2 Ah
9 Ah
(2)
5594-2BX
Operating temperature: 0 to +40 °C (32 to 104 °F)
Storage temperature: -15 to +50 °C (5 to 122 °F)
Relative humidity: 20 to 90 % (without condensation)
Noise level: < 45 dBA
5594-3KX
50/60Hz, 1ph;
200VAC, 2700VA,
2430W, 13.5A;
208VAC, 3000VA,
2700W, 14.5A;
220VAC, 3000VA,
2700W, 13.7A;
230VAC, 3000VA,
2700W, 13.0A;
240VAC, 3000VA,
2700W, 12.5A
(1)
6 x 12V
9Ah
(3)
5594-3BX
Noise level: < 50 dBA
Appendix A. Specifications
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rt3.0kvaRt2.2kva

Table of Contents