Lenovo RT1.5kVA Installation And User Manual page 30

2u rack or tower ups
Hide thumbs Also See for RT1.5kVA:
Table of Contents

Advertisement

14
Installation and User's Guide
Table 1. User settings (continued)
Submenu
In/Out settings
Output voltage
Input thresholds
Sensitivity
Available settings
Default settings
Low voltage: [100 V]
Low Voltage model:
[120 V] [125 V]
110 V
High voltage: [200 V]
High Voltage model:
[208 V] [220 V] [230
230 V
V] [240 V]
User selectable when
UPS is powered for
the first time.
[Normal mode]
[Normal mode]
[Extended mode]
Extended mode
authorizes lower
input voltage (70 V)
without transferring
to battery. This can
be used if the load
can withstand low
voltage supply.
[High]
[High] [Low]
High: for sensitive
equipment, UPS will
easily transfer to
battery when utility
conditions are
becoming bad.
Low: for equipment
that can withstand
bad utility
conditions, in that
case, the UPS will
not transfer to
battery.