  • Page 1 Centurion 6000/10000 VA Rack Online UPS Users Manual www.powershield.com.au...
  • Page 2 Introduction Thank you for choosing PowerShield. PowerShield Centurion UPS series are designed to provide the highest level of protection against disturbances found on electrical power supply lines. It is suitable for most applications including IT, security, telephone, broadcasting, medical etc.
  • Page 3 Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully. www.powershield.com.au...
  • Page 4: Table Of Contents

    PERATING TATUS ESCRIPTION 3-8. F ......................19 AULT 3-9. W ....................21 ARNING NDICATOR 4. TROUBLE SHOOTING..................23 5. SERVICE…………………………………………………………………………………………24 6. CONTACTING PowerShield…………………………………………………………………24 7. STORAGE AND MAINTENANCE ................25 7-1. S ......................25 TORAGE 7-2. M ....................... 25 AINTENANCE 7. SPECIFICATIONS....................26 www.powershield.com.au...
  • Page 5: Safety And Emc Instructions

    UPS in any mode of operation should be provided in the building wiring installation. Connect the earth before connecting to the building wiring terminal. Installation and Wiring must be performed in accordance with the local electrical laws and regulations. www.powershield.com.au...
  • Page 6: Operation

    CS............:IEC/EN 61000-4-6 Level 3 Power-frequency Magnetic field....:IEC/EN 61000-4-8 Level 3 Low Frequency Signals......:IEC/EN 61000-2-2 Warning: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances. www.powershield.com.au...
  • Page 7: Installation And Operation

    Unpack the package and check the package contents. The shipping package contains: ● One UPS ● One user manual ● One PowerShield NetGuard UPS monitoring software CD ● One RS-232 cable ● One USB cable ● One EPO plug ( Fitted on the rear panel ) NOTE: Before installation, please inspect the unit.
  • Page 8: Single Ups Installation

    Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!) www.powershield.com.au...
  • Page 9: Software Installation

    ● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse and short-circuited. 2-4. Software Installation For optimal computer system protection, install PowerShield NetGuard UPS monitoring software to fully configure UPS shutdown. www.powershield.com.au...
  • Page 10: Operations

    ○ ○ Battery mode ● ○ ○ ○ CVCF mode ● ● ● ○ Battery Test ● ● ○ ○ ECO mode ● ○ ○ ○ Fault ● ○ Note: means LED is ON, and means LED is OFF. www.powershield.com.au...
  • Page 11 Indicates the load or the output is short. Programmable output information Indicates that the programmable outputs are working. Mode operation information Indicates the UPS connects to the mains. Indicates the battery is working. Indicates the bypass circuit is working. www.powershield.com.au...
  • Page 12: Audible Alarm

    Inverter soft start failure High Inverter voltage Low Inverter voltage Inverter output short circuited Beeping continuously Negative power fault Battery SCR short circuited Inverter relay short circuited Battery voltage loss Parallel communication failure Output short circuited Over temperature CPU communication failure Overload www.powershield.com.au...
  • Page 13: Ups Operation

    2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time. 3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to real connection. www.powershield.com.au...
  • Page 14 2) Then UPS will cut off power to output and there is no display shown on the display panel. 9. Mute the buzzer 1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the buzzer is muted, the buzzer will beep again. www.powershield.com.au...
  • Page 15: Abbreviation Meaning In Lcd Display

    5) Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS. 3-5. Abbreviation Meaning in LCD Display Abbreviation Display content Meaning Enable Disable Auto Battery Normal mode (not CVCF mode) CVCF mode Subtract www.powershield.com.au...
  • Page 16: Lcd Setting

    Programmable output setting These functions are not supported by the Rack model Shutdown point for programmable output Reserved for future setting Battery voltage adjustment Charger voltage adjustment Output voltage adjustment *Y means that this program can be set in this mode. www.powershield.com.au...
  • Page 17 60 Hz system: Setting range is from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz. Parameter 3: Set the acceptable high frequency for bypass. 50 Hz: Setting range is from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz. The default value is 54.0Hz/64.0Hz. www.powershield.com.au...
  • Page 18 000~999: Set the maximum backup time from 0min to 999min. UPS will shut down to protect battery after backup time arrives. The default value is 990min. DIS: Disable battery discharge protection and backup time will depend on battery capacity. www.powershield.com.au...
  • Page 19 Reserve for future options. 13: Battery voltage adjustment Interface Setting Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure. Parameter 3: the voltage range is from 0V to 5.7V, the default value is 0V. www.powershield.com.au...
  • Page 20: Operating Mode/Status Description

    AC power to output. The UPS will also charge the battery at AC mode. LCD display ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled, UPS will bypass voltage to output for energy saving. LCD display www.powershield.com.au...
  • Page 21 I/P and inverter icons will blink to remind users. This operation is used to check the battery status. LCD display Fault status Description When UPS has fault happened, it will display fault messages in LCD panel. LCD display www.powershield.com.au...
  • Page 22: Fault Code

    Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure/Over temperature Beeping every second Charger failure Beeping every second I/P fuse broken Beeping every second Overload 3 times in 30min Beeping every second www.powershield.com.au...
  • Page 23: Trouble Shooting

    Contact your dealer to replace Batteries defect the battery. Fan is locked or not working; The icon flash on LCD or the UPS temperature is too Check fans and notify dealer. display and alarm beeps every second. high. www.powershield.com.au...
  • Page 24: Service

    5. Service WARRANTY CONDITION: The standard warranty is TWO (2) years from the date of purchase. The standard PowerShield procedure is to replace the original unit with a factory refurbished unit. PowerShield will ship the replacement unit once the defective unit has been received by the service department, or cross ship upon the receipt of a valid credit card number.
  • Page 25: Storage And Maintenance

    Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic. Please replace the fuse only with the same type and amperage in order to avoid fire hazards. Do not disassemble the UPS system. www.powershield.com.au...
  • Page 26: Specifications

    * Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. **If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. ***Product specifications are subject to change without further notice. www.powershield.com.au...
  • Page 27 37-100350-00G...