Samsung HHSM-G500005-1 Installation Manual page 52

Generation 5
Hide thumbs Also See for HHSM-G500005-1:
Table of Contents

Advertisement

Heat Pump
Please refer to controller symbols and button functions on pages 60 & 61 for further
guidance on the heat pump controls.
1. Ensure that both the outdoor and indoor units are correctly wired and plumbed
prior to turning on.
2. Flush the system at 110% of system flow rate in both directions using suitable
chemical.
3. Once the system has been power flushed you must now fill the system with Glycol.
4. The Glycol should be pre mixed before putting it into the system and a solar filling
station is ideal for filling the system, use the connections on the fill/flush and flow
meter to add the glycol.
5. Do not put Neat Glycol into the system, failure to do this may cause the glycol to
block the heat exchanger or block the pipes within the heat emitter circuit.
6. Run the solar filling station for at least an hour to purge all the air from the system.
7. Turn on power to the indoor unit first. Then turn on power to the outdoor unit
second.
8. The outdoor unit will start flashing numbers 00, 01,02, etc. It will then flash a
message like 00 00, dE, F0 etc
9. Once 00 disappears and the controller is just showing the time the system is then
ready for testing.
CHANGING THE BACK LIGHT SETTING
1. To change the back light setting from 5 seconds to 30 seconds push the user set
button once.
2. The controller will show 1, use the up arrow to change this to 4.
3. Push the right arrow twice and then change the 5 to 30 using the up arrow.
4. Push the set button once.
5. Push Esc to return to the normal screen.
52
Initial Start Up

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hhsm-g500016-1Hhsm-g500009-1Hhsm-g500012-1