Lp Conversion - Rheem *96V series Installation Instructions Manual

4 position condensing two-stage, communicating gas furnaces w/ecm blower
Table of Contents

Advertisement

NOTE: See Page 82 for Canadian High-Altitude
Derate.
The valve can be converted to use liquified petroleum (LP)
gas by replacing the pressure regulator springs with the
conversion kit springs. This LP kit spring allows the regula-
tors to maintain the proper manifold pressure for LP gas.
NOTE: Order the correct LP conversion kit from the fur-
nace manufacturer. Furnace conversion to LP gas must be
performed by a qualified installer, service agency or the
gas supplier.
ORIFICE INSTALLATION
LP Gas is a manufactured gas that has consistent heating
value across most regions.
The Sea Level input should still be reduced by 4% per
thousand ft. and the orifice size must be selected based on
the reduced input selection chart in High Alt. Instruction
Section.
To change orifice spuds for either conversion to LP or for
elevation:
1. Shut off the manual main gas valve and remove the
gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for proper op-
eration and manifold pressure.
5. Attach the notice label alerting the next service techni-
cian that the furnace has been converted to LP gas.
74
TABLE 13
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
10
20
30
1/2
275
189
152
3/4
567
393
315
1
1,071
732
590
1-1/4
2,205
1,496
1,212 1,039
1-1/2
3,307
2,299
1,858 1,559
2
6,221
4,331
3,465 2,992
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FERTIL-
IZER) EXCEPT LP GAS. THIS INCLUDES ALL DELIV-
ERY VESSELS (LP TRUCKS). IF MATERIAL OTHER
THAN LP GAS IS USED IN THE SAME
VESSELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE FUR-
NACE. THIS WILL VOID THE MANUFACTURER'S
WARRANTY. CONTACT THE SUPPLIER TO MAKE
SURE FERTILIZER IS NOT USED IN THE SAME
TANKS USED TO STORE AND DELIVER LP GAS.
FIGURE 38
TYPICAL LP KIT CONTENTS
Length of Pipe, Feet
40
50
60
70
80
129
114
103
96
89
267
237
217
196
182
504
448
409
378
346
913
834
771
724
1,417
1,275
1,181
1,086 1,023
2,646
2,394
2,205
2,047 1,921
90
100
125
150
83
78
69
63
173
162
146
132
322
307
275
252
677
630
567
511
976
866
787
1,811 1,606
1,496