Below are two lists; a list of standard operating codes and
a list of fault codes. The fault code list provides diagnostic
and troubleshooting information to help determine the
problem and fix it. Standard operating codes are not fault
codes and the presence of a standard operating code indi-
cates a no-fault condition.
TABLE 19
R96V NORMAL OPERATION CODES
Key
CODE
DISPLAYED
AT DUAL
SEVEN-
SEGMENT
DISPLAY OF
CONTROL
NORMAL OPERATION CODE
0
DESCRIPTION: This code is displayed anytime there is no fault present and no thermostat call present. The furnace is idle.
DESCRIPTION: This code is displayed anytime there is a call for gas heat. The lower-case "h" is displayed when the
H or h
thermostat is requesting low gas heat and the upper-case "H" is displayed when the thermostat is requesting high-stage gas
heat.
DESCRIPTION: This code is displayed anytime there is a call for cooling. The lower-case "c" is displayed when the thermostat
C or c
is requesting low-stage cooling and the upper-case "C" is displayed when the thermostat is requesting high-stage cooling.
DESCRIPTION: This code is displayed anytime there is a call for heat-pump heat. The lower-case "hP" is displayed when the
HP or hP
thermostat is requesting low-stage heat-pump heat and the upper-case "HP" is displayed when the thermostat is requesting high-
stage heat-pump heat.
F
DESCRIPTION: This code is displayed anytime there is a call for continuous fan from the thermostat.
dF
DESCRIPTION: This code indicates that the heat-pump is in defrost mode (dual-fuel systems only) and furance is operating for
defrost operation which is fixed at low-stage gas heating operation.
DESCRIPTION: This code indicates that there is a both cooling and dehumidication demand present at the same time. When
de-humidification is active, the cooling airflow will be reduced in order to allow water to accumulate on the condenser therby
Cd or cd
removing humidity from the conditioned environment. The lower-case "cd" is displayed when the thermostat is requesting low-
cooling with de-humidification and the upper-case "Cd" is displayed when the thermostat is requesting high-stage cooling with
de-humidification.
108
NOTE: Verify display orientation is correct before interpret-
ing fault codes. Otherwise, the fault codes may be upside-
down. If a fault code or operating code is not on these
lists, the display may be upside-down.

NORMAL OPERATION CODES

NAME
DESCRIPTION
STANDBY MODE
GAS HEAT MODE
COOLING MODE
HEAT-PUMP HEATING MODE
CONTINUOUS FAN MODE
DEFROST MODE
COOLING IN DE-HUMIDIFICATION MODE