Outdoor Unit - Panasonic CS-A7BKP Service Manual

Table of Contents

Advertisement

CS-A7BKP CU-A7BKP5 / CS-A7BKP CU-A7BKP6 / CS-A9BKP CU-A9BKP5 / CS-A9BKP CU-A9BKP6 / CS-A12BKP CU-A12BKP5 / CS-A12BKP CU-A12BKP6
10.3.5. (b) AIR PURGING OF THE PIPING AND INDOOR UNIT
The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compressor.
1. Remove the caps from the 2-way and 3-way valves.
2. Remove the service-port cap from the 3-way valves.
3. To open the valve, turn the valve stem of 2-way valve counter-clockwise approx. 90° and hold it there for ten seconds, then
close it.
4. Check gas-leakage of the connecting portion of the pipings.
For the left pipings, refer to item 4(A).
5. To open 2-way valve again, turn the valve stem counter-clockwise until it stops.
4(A). Checking gas leakage for the left piping.
(1) *
Connect the manifold gauge to the service port of 3-way
valve.
Measure the pressure.
*
10.3.6. CONNECT THE CABLE TO THE

OUTDOOR UNIT

1. Remove the control board cover from the unit by loosening
the screw.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7BK,
C9BK, C12BK, V7BK, V9BK, V12BK) or 5 (A7BK, A9BK,
A12BK, W7BK, W9BK, W12BK) × 1.5 mm
type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder
(clamper).
4. Attach the control board cover back to the original position
(2) *
with the screw.
2
flexible cord,
46
Keep it for 5-10 minutes.
Ensure that the pressure indicated on the gauge is the
*
same as that of measured during the first time.