9 Printed Circuit Board ------------------------------------------ 20 11.13. Random Auto Restart Control ------------------------ 48 9.1. Indoor Unit (Main Printed Circuit Board) ----------- 20 11.14. Remote Control Signal Receiving Sound---------- 48 9.2. Indoor Unit (Power Printed Circuit Board) --------- 22 11.15. Patrol Operation------------------------------------------ 49 9.3.
Page 3
8. When connecting the piping, do not allow air or any substances other than the specified refrigerant to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and injury.
2 Specifications 2.1. CS-A7GKD CU-A7GKD Item Unit Indoor unit Outdoor unit Performance Test Condition C Capacity 2.00 - 2.00 BTU/h 6820 - 6820 kcal/h 1720 - 1720 L EER 3.28 - 3.17 BTU/hW 11.2 - 10.8 N Noise Level dB (A)
Page 5
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.) 2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F D.B.), 6°C W.B.
2.2. CS-A9GKD CU-A9GKD Item Unit Indoor unit Outdoor unit Performance Test Condition C Capacity 2.65 - 2.65 BTU/h 9040 - 9040 kcal/h 2280 - 2280 L EER 3.19 - 3.08 BTU/hW 10.9 - 10.5 N Noise Level dB (A) High: 36 Low: 26 High: 48 - 49 Power level dB High: 49...
Page 7
Item Unit Power Source (Phase, Voltage, Cycle) ø Single Single Input power Cooling Heating Starting Current Running Current Cooling Heating Power Factor Cooling Heating Power factor means total figure of compressor, indoor fan motor and outdoor fan motor. Power Cord Number of core 3 (1.5mm) Length...
2.3. CS-A12GKD CU-A12GKD Item Unit Indoor unit Outdoor unit Performance Test Condition C Capacity 3.52 - 3.54 BTU/h 12000 - 12100 kcal/h 3030 - 3040 L EER 3.26 - 3.16 BTU/hW 11.1 - 10.8 N Noise Level dB (A) High: 39 Low: 29 High: 48 - 49 Power level dB High: 52...
Page 9
Item Unit Power Source (Phase, Voltage, Cycle) ø Single Single Input power Cooling 1.08 1.12 Heating 1.09 1.12 Starting Current Running Current Cooling Heating Power Factor Cooling Heating Power factor means total figure of compressor, indoor fan motor and outdoor fan motor. Power Cord Number of core 3 (1.5mm)
3 Features • High Efficiency • Compact Design • Wider range of horizontal discharge air • Air Filter with function to reduce dust and smoke • Automatic air swing and manual adjusted by Remote Control for vertical airflow • Long Installation Piping - CS/CU-A7GK, CS/CU-A9GK, long piping up to 10 meter - CS/CU-A12GK, long piping up to 15 meter •...
8.2. CS-A12GK CU-A12GK Resistance of Indoor Fan Motor Windings Resistance of Compressor Windings MODEL CS-A12GK MODEL CU-A12GK CONNECTION CWA921373 CONNECTION 2KS206D5AF04 390.0 Ω 2.234 Ω BLUE-YELLOW C - R 394.0 Ω 2.630 Ω YELLOW-RED C - S Note: Resistance at 25°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
11 Installation Instruction 11.1. Select The Best Location Indoor Unit Indoor/Outdoor Unit Installation Diagram • There should not be any heat source or steam near the unit. • There should not be any obstacles blocking the air circulation. • A place where air circulation in the room is good. •...
11.2. Indoor Unit 11.2.2. To Drill A Hole In The Wall And Install A Sleeve Of Piping 11.2.1. How To Fix Installation Plate 1. Insert the piping sleeve to the hole. The mounting wall is strong and solid enough to prevent it from 2.
Page 26
For the embedded piping Insert the connecting cable Install the Indoor unit Secure the Indoor Unit Pull out the piping and drain hose How to keep the cover (This can be used for left rear piping & left bottom piping also.)
• Secure the cable onto the control board with the holder (clamper). • How to pull the piping and drain hose out, in case of the embedded piping. • In case of left piping how to insert the connecting cable and 11.3.
Page 28
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3.
Page 29
CAUTION • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure: • If the leak stops when the piping connections are tightened further, continue working from step 3. •...
12 Operation and Control 12.1. Heating Operation • Heating operation can be set using remote control. • This operation is applied to warm the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
12.2. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
12.3. Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. •...
12.4. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. •...
• Automatic Set Temperature For each operation, set temperature will automatically set as shown below. However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Setting button”. • The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in below table by pressing on the temperature up or temperature down button at remote control.
Page 35
12.5.3. 7 Minutes Time Save Control • The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the compressor ON temperature (A) and compressor OFF temperature (B) during the period. • This phenomenon is to reduce the built up humidity inside a room. 12.5.4.
Page 36
12.5.7. Dew Prevention control • To prevent dew formation at indoor unit discharge area. • This control will be activated if:- - Cooling mode or Quiet mode. - Remote Control setting temperature is less than 25°C. - Fan speed is at CLo or QLo. - Room temperature is constant (±1°C) for 30 minutes.
Page 37
12.5.8. 30 Minutes Time Save Control • The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls between the compressor OFF temperature (A) and compressor ON temperature (B) during the period. • This is to maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air temperature due to poor installation near the sensor area.
Page 38
12.5.13. Anti Cold Draft Control • This operation is to prevent the Cold Draft during Heating mode operation. • The operation will start when compressor OFF (Thermo OFF) during Heating operation. • For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat exchanger temperature as shown below: •...
Page 39
12.5.14. Deicing Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deicing Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for 50 sec.
Page 40
Normal Deicing Time Diagram Overload Deicing Time Diagram...
12.6. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control. 12.6.1. Fan Speed Rotation Chart Fan Speed (rpm) CS-A7GKD CS-A9GKD CS-A12GKD S Hi 1190 1300 1320 1030 1210 1300 1000 1120 H Lo C Lo...
Page 42
• Auto Fan Speed during cooling operation: 1. Indoor fan will rotate alternately between off and on as shown in below diagram. 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose. 3.
• Auto Fan Speed during Heating operation. 1. Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature. 12.6.3. Manual Fan Speed Control • Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. •...
(Heating Operation condition) Heating Operation • When the piping air temperature reaches 38°C, the louver is changed from upper to lower limit. When the piping air temperature falls to 35°C, the louver is changed from lower to upper limit. 12.8.2. Manual Control •...
Page 45
• The Fan Speed will shift as shown below: • Vertical Airflow Direction:- - In “Manual” setting, the vane will automatically shift down 5° lower than previous setting. - In “Auto” setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as Heating Mode, Airflow Direction Auto-Control.
12.11. Quiet Operation (For Cooling Operation or cooling region of Soft Dry Operation) • To provide quiet cooling operation condition compare to normal operation. • Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce around 2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present operation sound level.
Page 47
(Heating Operation condition) • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB (Lo) or 3 dB (Hi, Me), against the present sound level operation. • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. •...
12.12. Timer Control 12.12.1. ON Timer • When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room • will reach nearly to the set temperature by the set time. •...
12.15. Patrol Operation 1. Purpose To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty. 2. Control Condition a. Patrol operation start condition • When the unit operation is started with “OFF/ON” button. •...
Page 50
3. Control Content a. Gas Sensor Control • First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is monitored. The Air Dirtiness level is set to level 2. • After that, gas sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air. •...
Page 51
c. Indoor Fan Control • During any operation mode combines with Patrol operation, fan speed follows respective operation mode. • During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan Speed”...
12.16. e-ion Operation 1. Purpose This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-ion filters. 2. Control Condition a. e-ion operation start condition • During unit running at any operation mode, if “e-ion” button is pressed, combination operation (operation mode + e-ion operation) starts.
Page 53
3. Control Content a. Indoor fan control • During any operation mode combines with e-ion operation, fan speed follows respective operation mode. • During e-ion individual operation - only Auto Fan Speed and no Powerful operation is allowed. Even if Fan Speed button is pressed, no signal is sent to air conditioner, and no change on LCD display.
Page 54
g. Error Detection Control When e-ion indicator blink, it indicates error listed below: a. e-ion AIR PURIFYING SYSTEM main connector to PCB is open: Judgment Method • During e-ion operation (include during Patrol operation), e-ion AIR PURIFYING SYSTEM main connector to PCB is opened.
13 Servicing Mode 13.1. Auto OFF/ON Button 1. AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be use to operate air conditioner with limited function if remote control is misplaced or malfunction. 2.
13.3. Remote Control Button 13.3.1. SET BUTTON • To check current remote control transmission code. - Press for more than 10 seconds. • To change the air quality sensor sensitivity: - Press and release with pointer. - Press the Timer Decrement button to select sensitivity: 1.
14 Troubleshooting Guide 14.1. Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.
Page 58
14.1.1. Relationship Between The Condition of The Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the air conditioner Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current during operation during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or Strainer...
15 Disassembly and Assembly Instructions WARNING • Cautions! When handling electronic controller, be careful of electrostatic discharge. • Be sure to return the wiring to its original position. • There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after power has been turned off.
17 Exploded View and Replacement Parts List 17.1. Indoor Unit Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 77
REF. NO. PART NAME & DESCRIPTION QTY. CS-A7GKD CS-A9GKD CS-A12GKD ← ← CHASSY COMPLETE CWD50C1513 ← ← FAN MOTOR, AC 15W SINGLE CWA921373 ← ← CROSS FLOW FAN COMPLETE CWH02C1045 ← ← BEARING ASS’Y CWH64K007 ← ← SCREW - CROSS FLOW FAN CWH551146 ←...
17.2. Outdoor Unit 17.2.1. CU-A7GK CU-A9GK Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 79
REF. NO. PART NAME & DESCRIPTION QTY. CU-A7GKD CU-A9GKD ← CHASSY ASS’Y CWD50K2112 ← SOUND PROOF MATERIAL CWG302255 ← FAN MOTOR BRACKET CWD541075 ← SCREW - FAN MOTOR BRACKET CWH551198 ← FAN MOTOR (AC 30W SINGLE) CWA951387J ← SCREW - FAN MOTOR MOUNT CWH55406J ←...
Page 80
17.2.2. CU-A12GK Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 81
REF. NO. PART NAME & DESCRIPTION QTY. CU-A12GKD CHASSY ASS’Y CWD50K2074 SOUND PROOF MATERIAL CWG302410 FAN MOTOR BRACKET CWD541030 SCREW - FAN MOTOR BRACKET CWH551198 FAN MOTOR (AC 30W SINGLE) CWA951117J SCREW - FAN MOTOR MOUNT CWH55406J PROPELLER FAN ASS’Y CWH03K1006 NUT - PROPELLER FAN CWH56053J...