Compressor Protection Control
• After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
• If the above phenomenon is repeated for 3 times, the compressor will stop totally.
• The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
Anti-Dew Formation Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When the following conditions occur for 30 minutes continuously, anti-dew formation is controlled by indoor fan speed shift to
low (CLo to HLo):
− Indoor intake air temperature is more than 24°C and less than 30°C.
− Remote Control setting temperature is less than 25°C.
− Compressor is on.
− Cooling operation mode.
− Indoor Fan motor operate at Low fan speed.
• This control is cancelled immediately when above condition is changed.
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.