CLEARANCE REQUIREMENTS
W.
Minimum alcove width
D.
Maximum alcove depth
G.
Alcove ceiling above stove top
FLOOR PROTECTION REQUIREMENTS
A.
Extending distance, back
B.
Extending distance, right side
C.
Extending distance, left side
D.
Extending distance, front
In the US, floor protection must be constructed of a non-combustible material and installed
to extend beneath the heater and 16'' to the front and 8'' to the sides of the fuel loading
door and ash removal openings. In Canada, floor protection must be constructed of a non-
combustible material and installed to extend beneath the heater and 450 mm.(16'') to any
side with a door and 200 mm.(8'') beyond the appliance on the other sides.
ALCOVE INSTALLATION
USA
56"
24"
36"
NON-COMBUSTIBLE MATERIALS
BENEATH STOVE
USA
-
6"
6"
16"
CANADA
1420 mm
610 mm
915 mm
CANADA
200 mm
200 mm
200 mm
450 mm