5.6.2 Error codes
Code
Description
A2001
Over current
A2002
Over voltage
A2003
Under voltage
A2006
Speed reference
error
A2009
Over
temperature
A5001
Internal error
F0001
Over current
F0002
Over voltage
F0003
Over
temperature
F0004
Short circuit in
motor
F0006
Under voltage
F0007
Speed reference
error
F0016
Protective earth
failure
F0018
Internal error
F0021
F0022
Power supply
phase fault
F0034
Motor phase
fault
Table 5-2Error codes
Alarm codes starts with "A" and fault codes starts with "F". The machine will be operational if an alarm
code is present but not when an fault code is present.
The following table describes the access for the task.
Abbreviation Person
O
Machine Operator
E
Electrician
S
Scanmaskin certified service technician
Table 5-3
Access rights for different persons
6
See access table "Table 5-3"
Cause
One of the three phases is missing from the
power supply
There is a voltage drop at the power supply
The environmental temperature is too high. When
the temperature is above 40°C (104°F) the
inverter will decrease its maximum output current
The power supply has got voltage transients
One of the three phases is missing from the
power supply
There is a voltage drop at the power supply
The potentiometer on the control panel is
damaged
The internal temperature in the inverter is above
120°C (248°F). This could be caused by faulty
ventilation in the electrical cabinet.
The internal temperature in the inverter is above
135°C (275°F). This could be caused by faulty
ventilation in the electrical cabinet.
The cable to the motor has been damaged
The motor has been damaged
The cable to the motor has been damaged
The motor has been damaged
Water have entered the motor
One of the three phases to the motor is missing.
This could be due to damage to the motor cable
or to the motor.
Correction
Inspect the fuses in the worksites fuse box
Inspect cables
Measure that all three phases are present and at
full voltage at the cable end near the machine
Make sure that the cable is not to long. If the
cable should be to long, use a cable with higher
rating to a distribution box nearer the machine
Inspect the ventilation fans
Inspect the filters to the fans
Inspect the power source
See A2001
Inspect the potentiometer
Replace if necessary
Inspect the ventilation fans
Inspect the filters to the fans
Contact Scanmaskin Sweden AB
Inspect the motor cable
Inspect the motor connection
Contact Scanmaskin Sweden AB
Inspect the motor cable
Inspect the motor connection
Contact Scanmaskin Sweden AB
Inspect the motor cable
Inspect the motor connection
Contact Scanmaskin Sweden AB
- 21 -
Contact Scanmaskin Sweden AB
See A2001
See A2002
See A2009
See A2003
See A2006
Contact Scanmaskin Sweden AB
See A2003