Installation instruction
<Installer Setting Code Table>
No.
Function
Code
1
Test Run
01
01:Set
2
Address Setting
02
00~FF : Address
<ESP Step>
01:VeryLow
02:Low
3
E.S.P. Value
03
03:Med
04:High
05:Very High
01:Remo
4
Thermistor
04
02:Indoor
03:2TH
01:Med
02:Low
5
Ceiling Height
05
03:High
04:Very High
01:V-H
02:F-H
6
Static Pressure
06
03:V-L
04:F-L
00:Slave
7
Group Setting
07
01:Master
00:Slave
8
Override Setting
08
01:Master
00:OFF
9
Dry Contact
09
01:ON
Release 3 Min.
10
10
01:Set
Delay
01:Variable
11
Zone State
11
02:Fixed
Celsius
01:Celsius
12
12
Fahrenheit Switching
02: Fahrenheit
00:Old
13
Zone Type
13
01:New
14
Zone Number
14
02~04(Zone number)
15
Plasma
20
16
Electric heater
21
00: Not Installed
17
Humidifier
22
01: Installed
18
Elevation Grill
23
19
Ventilation Kit
24
❊
Some contents may not be displayed depending on the product function
10 Wide Wired Remote Controller
Value
<ESP Value>
0 ~ 255
Function Code
ESP step
ESP value
(Optimized only for U.S.A)
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
1
2
❊
18˚C cooling, High Fan Speed, Airflow direction mode will be operated during 18 minutes with
ignoring room temperature.
❊
After running 18 minutes under test run mode, system will automatically turn OFF.
❊
In case of duct type, the Airflow UP/DOWN function is not displayed.
❊
During test run mode, receiving signal from wireless remote controller will release this operation.
If you press any kind of button, Test Run mode will be released.
Installation instruction
1
Keep pressing
button setting for 4
secs to enter installer setting mode until
code displayed in timer segment.
Function Code
Set
2
Press
button to start.
Owner's & Installation Manual 11